Inrush and breaker sizing: why it trips on switch-on
LED inrush comes from charging the input capacitor: the peak can reach 20–60 times rated current for under 1 ms. A breaker trips on the let-through energy, so one fixture is fine and a row switched on together is not. Three workable fixes: use type C or D (magnetic trip at 5–10 and 10–20 times) rather than type B; keep a 16 A circuit to about 8–12 fixtures, checked against the driver I²t and the breaker curve; and stagger the switch-on or specify soft-start drivers. On site, energise the row in two halves — if the trip disappears it is inrush, not a faulty fixture.
Get a QuoteKey parameters
| Power | 100–240 W |
|---|---|
| Luminous flux | 13,000–31,000 lm |
| Mounting height | 6–10 m |
| Input voltage | 220–240 V |
| Frequency | 50 / 60 Hz |
| Allowed voltage drop | ≤ 3% end to end |
| Inrush current | about 30–60 A cold start per fixture, under 1 ms |
| Breaker sizing | type C or D; about 8–12 fixtures per 16 A circuit |
Voltage is the item most often skipped
This page is 220–240 V at 50 / 60 Hz. Wide-range input is not about "works anywhere" — it is about not derating or tripping when the supply sits low or high. In regions with unstable grids, narrow-range drivers fail noticeably more often.
The other thing that gets skipped is inrush: when high-power fixtures start together the inrush adds up and trips the breaker. Where twenty units switch on at once, size the breaker on the row, not on one fixture — undersize it and the symptom is "it trips the moment you switch on", which few people trace back to the lights.
Voltage drop: right voltage, still dim
Allowed drop on this page is ≤ 3% end to end. It shows up worst on low-voltage and DC systems: a 24 V run of 30 m on 2.5 mm² can lose more than 10% by the far end, the fixtures visibly dimmer and the furthest ones dimmest. On site that looks like a faulty fixture; it is an undersized cable.
On the AC side the working figure is to keep total drop under 3%. That is a wiring parameter, not a fixture parameter — but it decides what the customer sees, so size the cable during the quote, not during commissioning when the lights get blamed.
Four things to verify before ordering
① Whether flux and efficacy are quoted for the complete fixture or the light source — a 10–15% difference that changes the fixture count. ② Whether colour temperature and CRI are measured or nominal values; mixed CCT within one batch is the most common arrival dispute. ③ Driver brand and model, plus its derating curve at high temperature — it is the only part that really sets life. ④ The mounting kit list: chain, bracket and anchors in the box, or the site stops for a day.